YSLCY-JZ 300/500V Command cable

Uses

» A flexible small-diameter cable for industrial use, in locations where there is electromagnetic interference.

» Compatible for moderate mechanical loads, for use in dry, humid, or wet areas.

» For use in machinery and production line construction, command, signaling, control and measurement.

» For permanent and mobile installation, on the condition that heavy mechanical stress is not applied on the cable.

» Thanks to the cable’s small diameter and its flexibility, it is compatible for use in narrow locations.

Technical Data and Conditions for Installation

» Work temperature: Up to +70°C

» Bending radius: 
In a permanent installation 10X the cable’s diameter and in mobile applications 20X the cable’s diameter.

» Maximum short-circuit temperature for 5 seconds: up to 150°C
 Work voltage: 300/500V
 Testing voltage: 2000V

» Compatible for indoor use, in dry, humid, or wet locations.

» Incompatible for indoor use, unless UV radiation protected and within the permitted range of temperatrures.

» The cable is not sensitive to random contact with fuel and oils, but not intended for constant submersion in them.

The Cable’s Structure

» Conductor: Flexible Class 5 Copper

» Strand insulation: PVC

» Color coding: Black numbered strands. One of the strands is yellow/green

» The strands are twisted in concentric layers and bound with plastic tape

» Shielding: Tin-plated copper braided mesh

» Outer shielding; PVC

» Color: Gray

Compatible Cable Types

» Command, Control (C2) Cables

Skip to content